Isolated DIN Rail Repeater/Splitter for Current Signals

DRSL-SP1

Isolated DIN Rail Repeater/Splitter for Current Signals | DRSL-SP1
Nouveau

Isolated DIN Rail Repeater/Splitter for Current Signals

149,00 DRSL-SP1

Garantie 1 an CE
  • Isolation and Conversion of Current Signals
  • Splitter Function: 1 Current Input—2 Current Outputs
  • Slimline Housing—Only 6 mm (0.24") Wide
  • Fast Response Time <7 ms
  • High Accuracy, <0.05% of Span
  • Easy-to-Use—No Setup Needed
Instruments de mesure et contrôle de processus - Voir Les Produits Associés

Déscription

The DRSL-SP1 isolated repeater/ splitter provides a competitive choice in terms of both price and technology for galvanic isolation of current signals to SCADA systems or PLC equipment. Two current outputs are provided which mirror the single current input.

The DRSL-SP1 can be used for signal conversion of a standard process current signal into two individual analog signals. The unit offers 4-port isolation, provides surge suppression and protects control systems from transients and noise. The DRSL-SP1 also eliminates ground loops and can be used for measuring floating signals. Low power consumption facilitates DIN rail mounting without the need for any air gap. Measurement ranges are factory calibrated. The unit operates over a wide temperature range from -25 to 70°C (-13 to 158°F).

SPECIFICATIONS
CURRENT INPUT
    Measurement Range: 0 to 20.5 mA
    Functional Range: 0 to 23 mA
    Input Voltage Drop: <1.5 Vdc

CURRENT OUTPUT
Number of Outputs: 2
    Signal Range: 0 to 20.5 mA (span)
    Load: 23 mA/300 Ω maximum
    Load Stability: ≤0.01% of span/100 Ω (span = 0 to 20 mA)
    Current Limit: ≤28 mA

GENERAL
Supply Voltage (via Power Rail or Connectors): 16.8 to 31.2 Vdc
Power Consumption: 0.8 W max
Internal Consumption: 0.4 W typical/0.65 W max
Isolation: Input/output 1/ output 2/supply
Isolation Voltage (Test): 2.5 kVac
Isolation Voltage (Working): 300 Vac
Signal/Noise Ratio: > 60 dB
Response Time (0 to 90%, 100 to 10%): <7 ms
Accuracy: < ±0.05% of span
Temperature Coefficient: <±0.01% of span/°C
EMC Immunity Influence: < ±0.5% of span
Extended EMC Immunity
    NAMUR NE 21, A Criterion, Burst:
<±1% of span

ENVIRONMENTAL
Operating Temperature: -25 to 70°C (-13 to 158°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Calibration Temperature: 20 to 28°C (68 to 82°F)
Relative Humidity: 0 to 95% RH non-condensing
Protection Degree: IP20
Installation Area: Pollution degree 2 and measurement/overvoltage category II

MECHANICAL
Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
Weight: 70 g (0.15 lb) approx
DIN Rail Type: DIN EN 60715 - 35 mm
Wire Size: 0.13 x 2.5 mm2/AWG 26 to 12 stranded wire
Screw Terminal Torque: 0.5 Nm
Placez votre commande(Veuillez spécifier la référence du produit)
Code d'article/ Desc.
Stock
Prix
Déscription
Qté
DRSL-SP1
Star
Stock: 1 semaine  
149,00   
Isolated repeater/splitter for current signals
 
Accessories
DRSL-PWR-RAIL
Star
Stock: 1 semaine  
97.00   
Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length
 
DRSL-PCU
Star
Stock: 1 semaine  
70.00   
Power connector unit, 24 Vdc/2.5 A output to power rail
 
DRSL-MOD-STOP
Star
Stock: 1 semaine  
4.40   
Module stop (screwed onto power rail to support and hold mounted devices)
 
Tous les Montants indiqués Dans EUR, GBP, USD.
Exemple de commande: (1) DRSL-MOD-STOP Module stop (screwed onto power rail to support and hold mounted devices), €4.40  plus (1) DRSL-PCU Power connector unit, 24 Vdc/2.5 A output to power rail, €70.00  plus (1) DRSL-PWR-RAIL Power rail (with cover and two end covers, one right hand and one left hand), 1 m (3.3') length, €97.00  plus (1) DRSL-SP1 Isolated repeater/splitter for current signals, €149.00, €4.40 + 70.00 + 97.00 + 149.00 = €320.40

Manuels de Produit:

Télécharger Installation Guide for Signal Conditioners
Télécharger DIN Rail Isolators and Signal Conditioners