€512,71 DPF302
                            
                            
                                    
                                      
                                    
                            Déscription
The DPF300 Series comprises
  4 to 20 mA loop-powered indicators that display process
  variables in engineering units
  (Bar, litres/min, °C, %RH, etc.), with
  an adjustable decimal point for rate
  and total display. Because these
  indicators take power directly from
  the current loop, the user can
  perform programming on the front
  keypad; there are no jumpers to
  configure or potentiometers to scale.
  An internal lithium battery ensures
  that all programming is retained in
  memory, even when the loop power
  is disconnected. The DPF301 can
  be programmed for either a linear
  input or square root extraction for
  use with differential pressure
  flowmeters.
  
  The DPF301 general purpose
  indicator features one 4½ digit rate
  display, while the DPF302 flow
  indicator has a dual, 2-line, 4½ digit
  rate display and 8-digit totaliser. The
  total count can be reset from either the
  front keypad or remotely via a
  contact closure.
  
  The DPF300 Series indicators
  are available in a choice of
  panel-mount, IP66 (NEMA 4X), or
  explosion-resistant enclosures.
  
  
  Specifications
  Scalable Input Range: 3.8 to 21 mA
  Rate Display (DPF301 and DPF302): selectable between 3½ and 4½ digits (19999), 9 mm  high
   Total Display (DPF302 Only): 8 Digits (99999999), 5 mm high
  Rate Descriptors: /sec, /min, /hr or "blank"
  Totaliser Unit Descriptors: Lit, Gal,  FT³, M³, "blank"
  Display Indications: Low battery and under/over range
  Input: 4 to 20 mA DC, overcurrent protection to 60 mA, reverse polarity protected
  Loop Voltage Drop: 6V max.
  Internal Battery (Memory Only): 3V 250 mAh lithium (2-year standby life)
  Housing:
      Standard: Round panel mount with IP66 sealed keypad membrane
      Optional: Glass-filled polycarbonate NEMA 4X (IP66) wall-mount enclosure, or wall/process mount explosion-resistant housing for NEMA 7, NEMA 4 (IP66), Class I, Groups B, C and D; Class II, Groups E, F and G
  Ambient Temperature: -20 to 70°C 
  Extended Temp Option: -30 to 70°C 
  Accuracy (@ 20°C): 0.1% FS resolution, ±1 count
  Temperature Drift: 50 ppm/°C typical, 200 ppm/°C worst case
  Low Cutoff: A rate below 1% of selected scale (10% of square root scale) will assume the "set lo" value
  Update Rate: For rate or total, once every 2 seconds
  Weight:
      Basic Unit: 227 g
      With IP66 Enclosure: 454 g
      With Explosion-Resistant Housing: 1.6 kg